R407C를 적용한 슬릿휜-관 열교환기의 증발특성에 관한 연구
김창덕(Chang-Duk Kim),장경근(Kyoung-Keun Jang),남임우(Leem-Woo Nam),전창덕(Chang-Duk Jeon),이진호(Jinho Lee) 대한기계학회 2001 대한기계학회 춘추학술대회 Vol.2001 No.9
This paper presents the evaporation characteristics of slit fin-tube heat exchanger installed into air-conditioning machines, due to the use of the alternative refrigerant. The experiments were conducted in order to investigate the effects of the temperature glide and the length of two phase region for ternary non-azeotropic refrigerant mixture R407C, which is one of the potential candidates for pure refrigerant R22. Test were conducted in a closed loop wind tunnel. The evaporation temperature of the refrigerant at the test section inlet were maintained at 7℃. The data covers a range of refrigerant mass fluxes 150-250 ㎏/㎡s supplied with air flows at velocities in the range 0.6-1.6 ㎧.