Performances of the Effervescent Atomizer for Water Mist Fire Extinguishing
( Jin Xiang Wu ),( Qiang Liang ),( Lian Sheng Liu ),( Yun Zhong Yan ),( En Yu Wang ),( Qing Miao ) 한국액체미립화학회 2005 한국액체미립화학회 학술강연회 논문집 Vol.2005 No.-
Based on the mechanism of effervescent atomization, a new effervescent atomization system of water mist was designed. In this system, the gas medium is carbon dioxide, which is soluble and can be used in fire suppression. High pressure saturated carbon dioxide-water solution flowed through the throttle orifice, carbon dioxide was bubbled, and the two-phase flow was formed in the mixing chamber of nozzle. At last, the water mist was formed downstream of the exit orifice of nozzle. In order to examine the feasibility of this system, data were collected, processed and analyzed with DUAL PDA. The velocity profile and drop-size distribution (D10, D32, Dv0.9) downstream of the effervescent atomizer were gained. The efficiency of fire suppression of this system were experimentally investigated by putting out the fire of industry alcohol and diesel oil. The experimental results showed that this water mist system is feasible for fire suppression.