Low GWP 냉매를 적용한 수열원 히트펌프 시스템의 난방성능 특성에 관한 실험적 연구
최연성(Youn Sung Choi),강희정(Hee Jeong Kang),김은오(Eun Oh Kim) 대한설비공학회 2018 대한설비공학회 학술발표대회논문집 Vol.2018 No.6
In this study, performance characteristics of a water source heat pumps system using R452B as a alternative refrigerant are experimentally investigated. The performance of the heat pump adopting R452B was also compared with the system applying R410A. Heating capacities and COP of the R452B system are analyzed for system performance variables such as refrigerant charge, load temperature conditions. Results show that optimum amount of refrigerant charge at maximum point of COP curve. The heating capacity of R452B heat pump system showed a slightly lower values within 1% comparing with R410A system. The R452B system’s coefficient of performance was enhanced by 5% at heating mode.